A steam heating system is a boiler that boils water into low pressure steam, which rises through pipes to radiators, condenses there to release its heat and drains back to the boiler by gravity. Most home systems are set to run from a few ounces to about 2 psi; 15 psig is the ceiling, not the target.
How does a steam heating system work, from burner to radiator?
The burner boils water, steam pushes air out through vents, condenses in the radiators and drains back by gravity, with no pump; hydronic hot water heating pumps liquid water instead.
- Controls agree. The burner lights only if the low-water cutoff senses water and the pressuretrol is below its setting.
- Steam rises into a header at least 24 inches above the waterline (Weil-McLain EG manual 550-142-303).
- Vents let air out and close when steam arrives; Peerless calls the main vent “the heart of a one-pipe system.”
- Radiators heat: each square foot of equivalent direct radiation (EDR) gives 240 BTU/h with 215°F steam in 70°F air (Weil-McLain).
- Condensate returns through the Hartford loop, connected about 2 inches below the water line (Bell & Gossett TES-375A).
What pressure should a home steam boiler run at, and what is the 15 psig limit?
Run it low: maker settings put a house system between a few ounces and about 2 psi. The 15 psig figure is the ceiling for a low-pressure steam boiler, and a gauge near it means something has failed.
| Pressure | What it is | Document |
|---|---|---|
| 0 to 16 oz/in² | Range of a Vaporstat control made “primarily for use in vapor heating systems” (16 oz/in² equals 1 psi) | Honeywell L408J product page |
| 2 psi main, 1.5 psi differential | Pressuretrol setting at start-up | U.S. Boiler Company SteamMax manual 111043-01, section 10 |
| around 2 psig | Where one pipe systems “should operate” at the boiler | Peerless One-Pipe Steam guide |
| no more than 2 psi; 2 to 5 psi typical | Recommended dry steam pressure vs. what many buildings are set to | DOE Building America |
| 10 PSIG | Highest setting allowed for the limit control | Weil-McLain EG manual 550-142-303 |
| 15 psig | Owner’s daily check: the gauge “does not exceed 15 psig”; higher means a bad gauge or limit control | Weil-McLain User’s Information Manual (CGa, CGi, EG, EGH, LGB, PEG) |
| 15 psi | Maximum allowable working pressure and highest relief valve setting | SteamMax manual |
| 15 psig | A low pressure steam boiler “operates at or below 15 pounds psig” | 10 CFR 430.2 |
| over 15 psig | High-pressure boiler class for state licensing | Minnesota DLI boiler safety guide |
Compiled by The HVAC Brief from the documents named. We did not read the paid ASME boiler code; the federal and Minnesota texts are the free statements of the 15 psig line.
Why low matters: Building America estimates that with a thermostatic valve shut, about 25% of a one pipe radiator still fills at 5 psi, against 12% at 2 psi. Maker settings are compared in our boiler pressure guide, and a gauge that sits high with water jumping in the glass is covered in steam boiler water level bouncing.

One pipe vs two pipe steam: which do you have?
Count the pipes at a radiator: one pipe carries steam in and condensate out; two pipe adds a return and a steam trap. Building America says one pipe systems are “commonly found in older buildings, especially those built before 1970.”
| Feature | One pipe steam | Two pipe steam |
|---|---|---|
| Pipes per radiator | One, shared by steam and condensate | Steam supply plus condensate return |
| How air leaves | Vent on each radiator plus main vents | Through traps to central vents |
| Thermostatic valve goes | On the air vent | At the radiator inlet |
| Classic fault | Clogged or stuck vent, hammer | Failed trap passing steam into the return |
Compiled by The HVAC Brief from DOE Building America and the Peerless guide. A one pipe vent that hisses after the radiator is hot is explained in steam radiator hissing; on two pipe systems a failed steam trap is the usual culprit. Banging usually means backpitched mains, which Building America says “can create low spots where water collects.”
Which safety controls must a steam boiler have?
A gauge glass, a low-water cutoff, a pressuretrol with a high-limit backup, and a relief valve. Minnesota’s boiler guide calls the low-water cutoff “the most important electrical/mechanical device on your boiler for maintaining a safe water-level,” and tells licensed operators to test it at least weekly. Weil-McLain’s EG manual calls for a monthly relief valve test in the heating season, and DOE’s archived Energy Saver page lists draining the float chamber.
How often should you add water to a steam boiler?
In a tight system, almost never. U.S. Boiler Company’s SteamMax manual tells owners to have the system checked for leaks if the boiler needs more than 0.01 to 0.03 gallons a month, or 0.13 to 0.31 gallons a year depending on size, a limit “based on maximum leak rate of 2% steamable water per month.”
What you check often is the level. Weil-McLain puts it “approximately ½ way up gauge glass” and tells installers to “avoid adding raw makeup water.” Peerless warns that new boilers hold less water and “can usually only steam for about 15 minutes” before reaching the low water point. The fill itself is covered in how to add water to a steam boiler.
An automatic feeder hides the leak, and Weil-McLain warns that boilers with one “could overfill.” SteamMax requires water treatment when a lot of make-up is used, with make-up capped at 30 ppm chlorides and 100 ppm hardness.
Is steam heat more expensive to run, and how long does a steam boiler last?
Yes, per unit of heat, and it wears out sooner. DOE’s archived Energy Saver page calls steam boilers “inherently less efficient,” and DOE’s 2023 analysis notes that “all steam boilers on the market are non-condensing.”
| Boiler class | Federal minimum, made since Jan. 15, 2021 | DOE max-tech AFUE | DOE average life | DOE installed cost | First-year operating cost |
|---|---|---|---|---|---|
| Gas steam | 82% | 83% | 23.7 years | $6,008 | $1,078 |
| Gas hot water | 84% | 96% | 26.9 years | $6,214 | $1,344 |
| Oil steam | 85% | 86% | 19.6 years | $6,977 | $2,726 |
| Oil hot water | 86% | 88% | 25.6 years | $6,945 | $2,783 |
Compiled by The HVAC Brief from 10 CFR 430.32(e)(2) and DOE’s proposed rule 88 FR 55128 (Table IV.4 and baseline life-cycle cost rows, 2022 dollars). DOE withdrew that proposal on January 17, 2025 (90 FR 5746), so treat these as DOE averages, not prices. Operating cost covers energy, maintenance and repair.
Our arithmetic: a new gas steam boiler at 82% AFUE burns 2.4% more gas than an 84% hot water boiler for the same delivered heat (84 ÷ 82), and 15.9% more than a 95% condensing one (95 ÷ 82). When the boiler is due, size it fresh: the Heating Helper says “a significant portion of existing boilers are mildly to grossly oversized,” and our boiler replacement guide covers the quotes.
What size steam boiler do I need for my radiators?
Size it by radiation, not floor area: add every radiator’s EDR, then pick a boiler whose net AHRI steam rating in square feet is at least that total. Weil-McLain’s Boiler Replacement Guide gives a worked example: a tube radiator 20 inches high, 7 inches wide, 4 tubes, 8 sections. Its Table F gives 2¼ sq ft per section, so 2¼ × 8 = 18 sq ft of EDR, and 18 × 240 = 4,320 BTU/h.
| Weil-McLain EG model | Net steam rating (sq ft EDR) | Net (MBH) | Gross steam output (MBH) | Gross ÷ net |
|---|---|---|---|---|
| EG-30 | 196 | 47 | 62 | 1.32 |
| EG-45 | 388 | 93 | 124 | 1.33 |
| EG-55 | 521 | 125 | 166 | 1.33 |
| EG-75 | 733 | 176 | 234 | 1.33 |
Weil-McLain EG/PEG series 6 manual, Table 16 (0 to 2,000 ft). Last column is HVAC Brief arithmetic; the manual’s 1.333 piping and pick-up allowance is already in the net rating, so do not add it again. The same radiators give far less on hot water: the Heating Helper’s capacity table drops from 240 BTU/h per sq ft on steam to 170 at 180°F water and 70 at 130°F.
Radiator EDR and steam boiler size calculator
Add every radiator on the system. Pick its type, then its height, then count the sections. Ratings are Weil-McLain’s Table F values from its Boiler Replacement Guide.
Pick a boiler whose net steam rating in sq ft is equal to or greater than the total; the net rating already includes the 1.333 allowance. Add the loss of any uninsulated steam mains, or insulate them. Hot water figures show what the same radiators would give after a conversion, from U.S. Boiler Company’s Heating Helper, which says to size a converted system’s boiler on calculated heat loss, not installed radiation.

Should you keep, tune or convert a steam heating system?
Tune it if it works; consider converting when the boiler is due. In a 2009 NYSERDA case study (archived copy), four New York apartment buildings that replaced steam boilers with hydronic boilers averaged 40.5% heating savings, while three that installed new steam boilers averaged 0.6%.
Going electric is harder: DOE’s 2024 boiler electrification guidance says steam must often be converted to hot water first, though one of its case studies, a 1926 ten-unit building, replaced a one pipe oil-fired steam boiler with ten 3-ton cold-climate heat pumps.
How we researched this
Upgraded November 27, 2026 (first researched October 8, 2026). We re-opened every document listed below, corrected the publisher of the SteamMax manual and Heating Helper (U.S. Boiler Company, not Burnham) and separated the operating setting from the 15 psig ceiling. We cut the full radiator tables and figures we could not re-trace; the radiator EDR calculator stays, its Table F ratings re-checked against page 10 of the Weil-McLain guide and its boiler pick taken from EG Table 16. Excluded: contractor price pages, a Canadian apprenticeship text and the paid ASME code.
Frequently asked questions
Can you bleed a steam radiator?
No. A steam radiator lets air out through an automatic vent that closes when steam arrives. DOE’s Building America guide pairs slow radiator vents with fast vents at the ends of the mains so all radiators start filling with steam at about the same time.
Can a heat pump work with steam radiators?
Not directly. DOE’s 2024 guidance says air-to-water heat pumps deliver water at 120 to 130°F, against about 180°F from a boiler, and that steam distribution must often be converted to hot water first, because radiators give far less heat at those temperatures.
What does EDR mean on a steam boiler?
EDR is equivalent direct radiation, the square feet of radiator surface a steam boiler can serve. Weil-McLain rates one square foot of EDR at 240 BTU/h with 215°F steam in 70°F air, and the boiler’s net AHRI steam rating in square feet must equal or exceed the total EDR connected to it.
Are steam heating systems still installed?
Yes. 10 CFR 430.32 still sets an 82% AFUE minimum for gas-fired steam boilers made on or after January 15, 2021, and a 2009 NYSERDA case study found New York apartment buildings as recent as five years old designed and built with steam boilers.
Sources
- U.S. Boiler Company. “SteamMax Installation, Operating and Service Instructions,” 111043-01, 3/21 (F.W. Webb copy). https://fwwebbimage.fwwebb.com/ProductInfo/SteamMax-IO-Manual.pdf. Accessed November 2026.
- U.S. Boiler Company. “The Heating Helper,” 2024-2025 edition. https://s3-us-west-2.amazonaws.com/catsy.782/Heating+Helper.pdf. Accessed November 2026.
- Weil-McLain. “CGa, CGi, EG, EGH, LGB, PEG Gas-Fired Boilers, User’s Information Manual.” https://www.weil-mclain.com/wp-content/uploads/egh-user-manual_1.pdf. Accessed November 2026.
- Weil-McLain. “EG/PEG Series 6, EGH Series 5 Boiler Manual,” 550-142-303/1120. https://www.weil-mclain.com/wp-content/uploads/EG-PEG-Series-6-Boiler-Manual-Web-Version.pdf. Accessed November 2026.
- Weil-McLain. “Boiler Replacement Guide.” https://www.weil-mclain.com/wp-content/uploads/Weil-McLain_BoilerReplacementGuide_WM2012-web_0-1.pdf. Accessed November 2026.
- Peerless (PB Heat). “One-Pipe Steam Systems: Piping and Troubleshooting,” CHOS396 R2. https://www.peerlessboilers.com/wp-content/uploads/2018/01/OnePipeSteam.pdf. Accessed November 2026.
- Bell & Gossett. “Steam Heating Application Manual,” TES-375A. https://documentlibrary.xylemappliedwater.com/wp-content/blogs.dir/22/files/2012/08/tes-375a.pdf. Accessed November 2026.
- Honeywell. “Vaporstat Controllers L408J.” https://process.honeywell.com/us/en/products/thermal-solutions/fuel-and-air-delivery/pressure-switches-and-gauges/vaporstat-controllers-l408j. Accessed November 2026.
- eCFR. “10 CFR 430.2, Definitions” and “10 CFR 430.32, Energy and water conservation standards.” https://www.ecfr.gov/current/title-10/chapter-II/subchapter-D/part-430. Accessed November 2026.
- Minnesota Department of Labor and Industry. “Boiler safety.” https://www.dli.mn.gov/sites/default/files/pdf/boiler-safety.pdf. Accessed November 2026.
- U.S. Department of Energy. Consumer boilers proposed rule, 88 FR 55128 (August 14, 2023), and withdrawal, 90 FR 5746 (January 17, 2025). https://www.federalregister.gov/documents/2023/08/14/2023-16476/energy-conservation-program-energy-conservation-standards-for-consumer-boilers. Accessed November 2026.
- DOE Building America Solution Center. “Thermostatic Radiator Valves on Steam Heating Systems” and “Steam System Balancing for Multifamily Existing Buildings.” https://basc.pnnl.gov/resource-guides/thermostatic-radiator-valves-steam-heating-systems. Accessed November 2026.